TY - GEN
T1 - Controller design for dynamic voltage restorer with harmonics compensation function
AU - Cho, Young Hoon
AU - Sul, Seung Ki
PY - 2004
Y1 - 2004
N2 - This paper describes the design of the control loop of a enhanced Dynamic Voltage Restorer (DVR) controller which can handle power quality problems from not only voltage sag/swell but also harmonics. A novel controller, which has a feed-forward loop and two feed-back loops, is proposed. A feed-back loop is used to actively increase the damping component of LC filter system to keep the output voltage overshoot within allowable range, while a feed-forward loop is used to compensate the voltage drop due to the feedback loop. Another feed-back loop based on the digital repetitive control algorithm is implemented to compensate the periodic harmonics of load voltage, which may come from the source, power converter, and nonlinear load. The feasibility of the proposed DVR controller has been verified by the computer simulation results and also by experimental results on 5kVA DVR system under the various source and load conditions. The both results reveal satisfactory performance not only against sag/swell but also against harmonics.
AB - This paper describes the design of the control loop of a enhanced Dynamic Voltage Restorer (DVR) controller which can handle power quality problems from not only voltage sag/swell but also harmonics. A novel controller, which has a feed-forward loop and two feed-back loops, is proposed. A feed-back loop is used to actively increase the damping component of LC filter system to keep the output voltage overshoot within allowable range, while a feed-forward loop is used to compensate the voltage drop due to the feedback loop. Another feed-back loop based on the digital repetitive control algorithm is implemented to compensate the periodic harmonics of load voltage, which may come from the source, power converter, and nonlinear load. The feasibility of the proposed DVR controller has been verified by the computer simulation results and also by experimental results on 5kVA DVR system under the various source and load conditions. The both results reveal satisfactory performance not only against sag/swell but also against harmonics.
KW - DVR
KW - Harmonics
KW - Repetitive controller
KW - Sag/swell
UR - https://www.scopus.com/pages/publications/10944272183
U2 - 10.1109/IAS.2004.1348662
DO - 10.1109/IAS.2004.1348662
M3 - Conference contribution
AN - SCOPUS:10944272183
SN - 0780384865
T3 - Conference Record - IAS Annual Meeting (IEEE Industry Applications Society)
SP - 1452
EP - 1457
BT - Conference Record of the 2004 IEEE Industry Applications Conference; 39th IAS Annual Meeting
T2 - Conference Record of the 2004 IEEE Industry Applications Conference; 39th IAS Annual Meeting
Y2 - 3 October 2004 through 7 October 2004
ER -